D10024
D10024 Operator’s Guide
Copyright © 2001 Radionics Page 17 46521C
4.4.2 Time Setting
Select 3) Time from the Main Menu to change the time displayed on the D10024.
4.4.3 Enable/Disable Functions
Main Menu option four, 4) Enable, opens the Enable Menu. Main Menu option five, 5) Disable, opens the Disable Menu.
ENABLE: 1) Zone 2) Input 3) Keys
4) Day Mode 5) Outputs
DISABLE: 1) Zone 2) Input 3) Keys
4) Day Mode 5) Outputs
Figure 14: Enable/Disable Menus
The content of the Enable and Disable menus is identical, allowing the operator to enable or disable zones, individual
devices (input), panel keys, day modes and outputs (relays).
Note: NAC devices such as bells, horns and strobes cannot be enabled or disabled from Control Level 2.
4.4.3.1 Enable/Disable by Zone
To enable or disable input signals from devices by zone, select the first option, 1) Zone, from the Enable or Disable
Menu.
The display will prompt for the zone number. Key in the zone number and press the [Enter] key.
The display will repeat the zone number and ask “OK?”. Press the [Yes] key to confirm. The panel will then enable or
disable all the input devices in the selected zone.
Note: Any disabled circuit-driven device or relay on a circuit will still operate on output as programmed. Only the input signal
will be disabled. However, manual pull stations (alarm boxes) within the zone are not disabled.
When a device is disabled, the amber Point Bypassed LED on the LED display will light. The amber Trouble LED in the
corresponding zone of the Zone/Area display will also light, and the panel will display a disable message on the
alphanumeric display.
4.4.3.2 Enable/Disable Individual Detection Devices (Inputs)
To enable or disable input signals from individual detection devices, select 2) Input from the Enable/Disable Menu.
The display will prompt for the polling circuit (loop) number (1-5). Key in the circuit number and press [Enter].
The display will then prompt for the address of the device. Key in the address and press [Enter].
The display will then repeat the circuit number and address. Press the [Yes] key.
Note: Any disabled circuit-driven device or relay on a circuit will still operate on output as programmed. Only the input signal
will be disabled.
4.4.3.3 Enable/Disable Panel Keys
To enable panel keys, press any of the control keys except the [No] key, or press the [>] key.
The panel will prompt “Do you want to enable the control keys?”. Press the [Yes] key.
The panel then prompts for the Control Level 2 passcode. Key in the appropriate passcode.
The panel keys will be enabled for the programmed period of time. The display reverts to the Main Menu (see Figure
13). After one minute, the display reverts to the normal display. Pressing the [System Reset] key will also return the
display to the normal display.
To disable the panel keys, select 3) Keys from the Disable Menu. The display indicates that the panel keys are inhibited
and then returns to the normal display. Disabling the panel keys returns the D10024 to Control Level 1.
Control Level 2